Main function

1.Startup mode:   a. Current limiting startup: low down the start voltage and limit the start current by keypad setting and random adjusting.  b. Voltage ramp startup: smooth start for motor, reduce the concussion of electric network by start current.  c. Kick startup2.Stop mode: Free stop and Soft stop3.Control mode: keypad control, terminal control and PC/PLC control by MODBUS.4.System control function  a. Intelligentized--The output and input connect point is programmable. Internal intelligentized programs for loading.  b. Standard internal port (MODBUS) can realize computer control.  c. LED display. Operator can set all the parameter and program by keypad control.  d. Keypad control and remote control can switched over.  e. Delay output relay function.  f. Malfunction output relay function.  g. One softstarter controls more than one motor.5.System protection function  a. Over current protection 
  b. Over-load protection
  c. Out-phase protection
  d. Overheat protection

Technical Specifications

ItemsDescription
Power supplyAC 400V±20%, 50/60Hz (It is supplied by interior, users need not supply power.)
Input power supplyAC 400V±20%, 50/60Hz
Applicable motorCommon asynchronism motor
Startup modeVoltage ramp startup (1~120 seconds), current limiting startup (150~400% Ie), voltage kick startup, jogging start
Stop modeFree stop, soft stop (1~60 seconds)
Relay outputDelay running output, fault output, full voltage output (by pass) [contact dot: 5A, 250VAC]
Startup frequencyAdvise: not exceeding fifteen times per hour
Protection functionOut phase, over-load, over current over-heating.
DisplayLED nixie tube showing present output frequency, types of faults, and parameters for the system and operation, LED indicators showing the current working status of softstarter.
Protection levelIP20
Cooling modeAir cooling
Installation modeHanging type
Environment conditionsEquipment LocationIn an indoor location, Prevent exposure from direct sunlight, Free from dust, tangy caustic gases, flammable gases, steam or the salt-contented, etc.
Environment Temperature-10°C~+50°C
Environment HumidityBelow 90% (no water-bead coagulation)
Vibration StrengthBelow 0.5g (acceleration)
Height above sea level1000m or below
Applicable motor15-500KW

 Product summary
ModelMatched MotorRated CurrentSturcture codeExternal Dimension (A×B×H)Mounting Size (W×L)Remarks
HFR20151530RC1200×220×370150×350Metal Hanging
HFR20222245RC1200×220×370150×350
HFR20303060RC1200×220×370150×350
HFR20373775RC1200×220×370150×350
HFR20454590RC1200×220×370150×350
HFR205555110RC1200×220×370150×350
HFR207575150RC2254×276.5×487.5200×424.5
HFR209090180RC2254×276.5×487.5200×424.5
HFR2110110220RC2254×276.5×487.5200×424.5
HFR2132132260RC2254×276.5×487.5200×424.5
HFR2160160320RC2254×276.5×487.5200×424.5
HFR2200200400RC3364.5×351.5×555322×475
HFR2220220440RC3555×364.5×351.5322×475
HFR2250250500RC3364.5×351.5×555322×475
HFR2280280560RC3364.5×351.5×555322×475
HFR2315315630RC3364.5×351.5×555322×475
HFR2355355700RC4475.5×317.5×660402×607.5
HFR2400400800RC4475.5×317.5×660402×607.5
HFR2450450900RC4475.5×317.5×660402×607.5
HFR25005001000RC4475.5×317.5×660402×607.5

 

 

 